Product Details
Place of Origin: CHINA
Brand Name: GCE
Certification: CE UL TUV
Model Number: RBMS07-S23-125A512V
Payment & Shipping Terms
Minimum Order Quantity: 2
Price: negotiable
Packaging Details: Bubble bag, foam, carton
Delivery Time: 20~25days
Payment Terms: T/T, L/C
Supply Ability: 1000sets/month
|
Voltage:
|
512V
|
Warranty Years:
|
3 Years For RBMS And 1 Year For BMU/PCBs
|
Rated Current:
|
125A Continuous
|
Application:
|
BESS, UPS And So On
|
MOQ:
|
2 Sets
|
Payment Terms:
|
T/T, L/C
|
Suitable:
|
LFP, NMC, LTO
|
BMU Range:
|
8S~24s
|
Insulation Withstand Voltage:
|
2800VDC <1mA 1min
|
|
Voltage:
|
512V
|
|
Warranty Years:
|
3 Years For RBMS And 1 Year For BMU/PCBs
|
|
Rated Current:
|
125A Continuous
|
|
Application:
|
BESS, UPS And So On
|
|
MOQ:
|
2 Sets
|
|
Payment Terms:
|
T/T, L/C
|
|
Suitable:
|
LFP, NMC, LTO
|
|
BMU Range:
|
8S~24s
|
|
Insulation Withstand Voltage:
|
2800VDC <1mA 1min
|
GCE 512V 125A Lifepo4 BMS battery management system for HV Lifepo4 LTO NCM Lithium batteries of UPS Solar ESS Home ESS Residential ESS Containerized ESS
High Voltage Master BMS:
![]()
Sample Drawings Of Standard Products:
![]()
Specification:
| Product Name | BMS(Battery Management System) |
| Model no. | RBMS07-S23-125A512V |
| protecting method | MCCB+Contactor |
| Rated Current range | -250A~250A(Max. 500A) |
| Voltage Range | 96V-1000V |
| Current Sampling Accuracy | 1.0%FSR |
| Communication interface with PCS | RS485/CAN |
| Communication interface with BMU | CAN |
| Communication interface with SBMS | RS485/CAN |
| Communication with monitoring software/EMS | Ethernet |
| Support IAP upgrade | Yes |
| Support HMI display and parameter | No(Optional plugin) |
| Insulation detection | Yes(Optional) |
| High voltage power module | Support DC start (optional) |
| Dry contact output (normally open) | No |
| Maximum qty of BMUs | 20 |
| Power | 24VDC(18~28V) |
| Power consumption | ≤20W |
| Size(W*H*D)mm | 3U (482*132*500) |
| Way out | Front |
| Tap center | Support(Optional) |
| Net weight | 23 kgs |
One complete set of HV 105S336V 125A BMS solutions includes:
1set Master BMS, Model#: RBMS07-S23-125A512V
7sets 15S Slave BMU Model#: BMU02B-N15S08T48F
7sets 15S Wire Harness, including voltage&temperature sampling wires,
BMU communication cables, Fan power wire.
![]()
Basic Functions:
Optional function: Insulation detection
Applicable to system voltage: ≧300V
HMI display: 3.5 inches(embedded inside the cabinet)
Stand-alone or parallel function: Set up before leaving the factory
Dry contact: Maximum 2 dry contact outputs
Power Consumption: ≤15W
Withstand voltage rating: 2800VDC <1mA 1min
Safety certification: Comply with CE
certification standards: Operating Temperature -20℃~60℃
Installation method: Suitable for standard 19-inch cabinet installation
Incoming and outgoing line mode: Front side in and front side out
Operating ambient humidity: 5%~75%RH
BMS SYSTEM STRUCTURE:
![]()
Applications:
![]()
Get More You Want:
Linkage for downloading specifications for Separated Master and Slave BMS, BMU:
GCE_RBMS specification--EN--V1.0.pdf
GCE 12-16S BMU-specification-UL-V1.0.pdf
Linkage for downloading of BMS demand information collection form:
high voltage BMS(HV BMS) info collection form EN2021-04.do...