Rs485 CAN Integrated BMS 65S-75S 50A For Home Storage Micro Grid Applications

Product Details

Place of Origin: China

Brand Name: GCE

Model Number: RBMS0760S100A

Payment & Shipping Terms

Minimum Order Quantity: 2

Price: USD 470-587 per pcs

Packaging Details: Cardboard Packaging

Delivery Time: 15 work days

Payment Terms: T/T, L/C

Supply Ability: 10000pcs per month

Get Best Price
Highlight:

CAN Integrated BMS

,

Integrated BMS 65S

Size:
410*240*78mm
Voltage:
208V-240V
Current:
50Amp
Communication:
Rs485 CAN
Balancing:
Passive 200mA
Weight:
8kg
Solution:
Overall Solution
Application:
BESS UPS Backup Power
Basic Module:
15S Battery Packs
Size:
410*240*78mm
Voltage:
208V-240V
Current:
50Amp
Communication:
Rs485 CAN
Balancing:
Passive 200mA
Weight:
8kg
Solution:
Overall Solution
Application:
BESS UPS Backup Power
Basic Module:
15S Battery Packs
Rs485 CAN Integrated BMS 65S-75S 50A For Home Storage Micro Grid Applications

Product Name: 65S-75S 50A integrated BMS

Application:

1. Home storage,

2. Island off-grid energy storage,

3. Micro-grid applications,

4. UPS power supply,

5. Power System 220V DC power supply

 

This is our the 4th generation high voltage bms.It's an overall bms solution, that is to say,You don't need professional technology to install our high-voltage BMS to form a complete battery system.

 

 

 

Rs485 CAN Integrated BMS 65S-75S 50A For Home Storage Micro Grid Applications 0

 

 

Our high voltage BMS has complete battery charge and discharge control logic and balance function between batteries. We can also set various parameters of the system according to the actual needs of customers to ensure the stability, reliability and efficient performance of the system.

Rs485 CAN Integrated BMS 65S-75S 50A For Home Storage Micro Grid Applications 1

Our integrated BMS has cheap, easy to install, stable, efficient features, welcome agents, distributors to establish cooperation relationship with us!

Rs485 CAN Integrated BMS 65S-75S 50A For Home Storage Micro Grid Applications 2

 

GCE BMS uses the resistor circuit to balance the cell. The cell voltage of the battery pack reaches 3.5V and the voltage of the cell is higher than the lowest single-segment voltage of 50mV, or the cell voltage exceeds 3.65V to turn on the equalization function. Time (except for overcharge and full charge) equalization stops.

 

Make the BMS in the shutdown state and complete the connection with the BMS. After the BMS is assembled, turn the micro disconnect switch on the chassis to "on", then press the start button (DC start), and the BMS will enter the self-test.If the self-test is normal, you can hear the sound of the contactor closing, the green light on the chassis is on for a long time (it will flash if there is external communication), and the start is completed.

After the system starts and starts normally, turn the micro disconnect switch to "off" to turn the BMS into shutdown / transport status. If the BMS is not used for a long time, the BMS must be in this state.

 

Rs485 CAN Integrated BMS 65S-75S 50A For Home Storage Micro Grid Applications 3

Technical Data Sheet
Item Specifications and parameters
System operating voltage range 120 - 370 VDC
Startup mode DC start
balance Equilibrium type Passive resistance equalization
Balanced current 100mA ± 10mA (when cell at 3.50V)
Sampling accuracy ± 2℃
Voltage sampling Sampling accuracy single cell ±20mV
Communication mode Can: 1 channel (communication with PCs / UPS)
RS485: 1 channel (communication with upper computer / PCS / UPS)
Display mode 6-digit LED indicator, including
1-bit fault indication, 1-bit operation indication, 4-bit SOC power indication
HMI display: optional 3.5 inch
Rated current 50A/100A
(be selected according to customer needs)
Short circuit protection Support 7.5KA 20ms
Maximum overload capacity 50A system transient: 70A/10S
100A system transient: 150A/10S
Alarm level one Level
Protection level two levels
Level 1 cut off charge / discharge
Level 2 micro cut-off switch, system power down
Power consumption ≤10W
Weight 4.5kg
Withstand voltage rating 1800VDC 1mA 1min
Safety certification Comply with CE certification standards
Operating temperature -20~60℃
Operating humidity range <90 RH(40℃±2℃)