Product Details
Place of Origin: China
Brand Name: GCE
Certification: CE/ROHS/MSDS
Model Number: RBMS-S20-250A-460.8V
Payment & Shipping Terms
Minimum Order Quantity: 2 Sets
Price: negotiable with bruceliu@hngce.com
Packaging Details: Corrugated Carton, bundles, pallets, wooden box
Delivery Time: 15-20 days
Payment Terms: FOB/CFR/EXW
Supply Ability: 1000pcs / month
|
Rated Current:
|
250A
|
Current Sampling Accuracy:
|
1%FSR
|
Parallel Loop Current Control:
|
Support
|
System Protection Parameter Setting:
|
Support
|
Power Consumption:
|
≤15W
|
Battery Charge And Discharge Management:
|
Support
|
HMI Display:
|
4.2-inch Or 7-inch External Screen
|
Battery String:
|
128S
|
Color:
|
Black, White(MOQ Requirements)
|
Communication:
|
CAN RS485 TCPIP
|
Rated Voltage:
|
460.8V
|
Balance:
|
Active Or Passive Optional
|
|
Rated Current:
|
250A
|
|
Current Sampling Accuracy:
|
1%FSR
|
|
Parallel Loop Current Control:
|
Support
|
|
System Protection Parameter Setting:
|
Support
|
|
Power Consumption:
|
≤15W
|
|
Battery Charge And Discharge Management:
|
Support
|
|
HMI Display:
|
4.2-inch Or 7-inch External Screen
|
|
Battery String:
|
128S
|
|
Color:
|
Black, White(MOQ Requirements)
|
|
Communication:
|
CAN RS485 TCPIP
|
|
Rated Voltage:
|
460.8V
|
|
Balance:
|
Active Or Passive Optional
|
4U rack-level high-voltage BMS supporting 15-rack parallel operation, engineered for UPS cabinets and commercial & industrial energy storage systems.
This is a rack-level controller, not a module-level board. GCE's 4U high-voltage RBMS governs an entire 144-cell LFP string at 460.8V nominal, acting as the middle tier of a BMU-RBMS-SBMS chain and allowing as many as fifteen such strings to feed one cluster controller without competing for current share.
The whole assembly fits a standard 19-inch frame at 482 × 180 × 500 mm and roughly 22 kg, with studs and cable entry on the front face. A pre-charge stage sits inside, together with a breaker able to clear 1000 V at 25 kA inside 20 ms, so trouble on one rack is dealt with locally rather than pushed onto the DC bus.
Two supply inputs, one tapped from the cells and one from site mains with mains taking precedence, keep the controller alive for logging and signalling even after the string itself is isolated. Thresholds are written during commissioning and locked afterwards. Around five thousand events remain in onboard storage, and an SD slot extends history down to individual cell level.
Signal routes are kept apart on purpose: CAN downward to the BMU boards, RS485 or CAN upward to the cluster layer, Ethernet to the monitoring host, RS485/CAN to the converter. Where another maker's PCS, inverter or UPS is already on site, the protocol layer is tailored per project instead of bolting on a gateway.
Voltage tier matters here. A 144S string belongs in the 750 V class, usable from 260 to 750 VDC, topping out at 525.6 V when each cell reaches 3.65 V and bottoming near 360 V at cut-off.
| Model | RBMS-S20-250A-460.8V |
|---|---|
| Cell arrangement | 144 in series, LFP chemistry, 3.2 V each |
| Nominal string voltage | 460.8 V |
| Voltage tier | 750 V class, working window 260 to 750 VDC |
| Ceiling and floor per cell | 525.6 V at 3.65 V, about 360 V at 2.5 V |
| Current rating | 250 A standard, 125 A or 160 A on request |
| Nominal DC throughput | 115.2 kW at 460.8 V and 250 A |
| Current sampling accuracy | 1 percent FSR |
| Self-consumption | 15 W or less on two-wire, 25 W or less on three-wire |
| Dielectric strength | 2800 VDC, leakage below 1 mA held for one minute |
| Insulation supervision | Optional, banks at 300 VDC and above |
| Enclosure rating | IP20 |
| Ambient temperature | Minus 20 to 45 degrees Celsius, output trimmed above 45 following the published curve |
| Humidity | 5 to 75 percent RH |
| Width by height by depth | 482 × 180 × 500 mm |
| Mass | About 22 kg |
| Mounting | 19-inch frame, 4U pitch |
| Termination | Front entry and front exit, M8×16 studs, 70 mm² conductor minimum |
| Links | CAN to BMU layer, RS485/CAN to converter and cluster layer, Ethernet to host software |
| Volt-free contacts | Up to two normally open channels |
| Log capacity | 5000 records |
| Finish | RAL 9005 black, sand grain |
| Standards met | GB/T 16935.1, GB/T 17626.2, GB/T 17626.5 |
| Approvals | CE under IEC 62477-1 and EN 61000-6-2 and 61000-6-4, plus RoHS |
Utility PV blocks, islanded grids, factory and commercial storage rooms, microgrids, UPS cabinets, and 220 or 240 V DC plant supply — wherever a 144-cell string needs its own brain before the site controller steps in.
Brand: GCE, built in China. One set minimum. Quotations through bruceliu@hngce.com. Packed in carton, bundle, pallet or wooden crate. Ready in 15 to 20 days. FOB, CFR, or EXW. Capacity: 1000 units monthly. Rating, display size, three-wire midline build, third-party converter protocols, and the companion cluster controller are all selectable.
Commissioning walk-through, threshold setting, protocol mapping, fault diagnosis, firmware updates, and handover training for integration teams.
144 LFP cells in series at 460.8 V nominal, and the cluster layer chains fifteen such racks.
No, order the 750 V tier covering 260 to 750 VDC.
115.2 kW at the 250 A rating and nominal voltage.
CE under IEC 62477-1 with EN 61000-6-2 and 61000-6-4, RoHS, plus the three GB/T standards listed.
One set, 15 to 20 days.
Supported through per-project protocol work.